三相電壓不平衡報警表
MS-V396AUB三相(xiang)電(dian)(dian)(dian)壓不(bu)平(ping)衡報(bao)警(jing)(jing)表可通過(guo)面板按(an)鍵整定PT參數,直觀(guan)顯(xian)(xian)示(shi)系統(tong)(tong)(tong)次運行電(dian)(dian)(dian)壓,三排數碼管可同時顯(xian)(xian)示(shi)三相(xiang)電(dian)(dian)(dian)壓值,同時具有(you)(you)上、下限報(bao)警(jing)(jing)輸出功能(neng)(neng)(neng),帶有(you)(you)不(bu)平(ping)衡差值測量報(bao)警(jing)(jing)功能(neng)(neng)(neng),監測三相(xiang)電(dian)(dian)(dian)壓的(de)(de)不(bu)平(ping)衡度,對(dui)系統(tong)(tong)(tong)設備的(de)(de)非(fei)正常運行提前(qian)預(yu)警(jing)(jing),顯(xian)(xian)示(shi)清(qing)晰美觀(guan),能(neng)(neng)(neng)直接(jie)取代傳統(tong)(tong)(tong)的(de)(de)模擬指針表,是適合工(gong)礦企(qi)業、民(min)用建筑、樓(lou)宇自動化等現代供配電(dian)(dian)(dian)系統(tong)(tong)(tong)的(de)(de)種高性能(neng)(neng)(neng)自動化儀表。
、三(san)相電壓不平衡報警表功(gong)能綜述
MS-V396AUB三相電壓不平衡報警表可(ke)通過面(mian)板(ban)按(an)鍵整定(ding)PT參數,直觀顯示系統次運行(xing)電(dian)壓,三排數碼管(guan)可(ke)同時顯示三相電(dian)壓值(zhi),同時具(ju)有上、下限報警輸出功能,帶有不(bu)平衡差值測量(liang)報(bao)警(jing)功能,監(jian)測三(san)相電(dian)壓的不(bu)平衡度,對(dui)系統設備的非正常運(yun)行提前預警(jing),顯示清晰美(mei)觀,能直接取(qu)代傳統(tong)的模擬指針(zhen)表(biao),是適合(he)工礦企(qi)業、民用建筑(zhu)、樓宇自動化等現代供(gong)配電系統(tong)的種高性能自動化儀表(biao)。
二(er)、三相(xiang)電(dian)壓不(bu)平(ping)衡報警(jing)表主要技(ji)術指(zhi)標
2.1、信號輸入:標稱輸入:AC 100V、400V
允許過量程:瞬時:10倍(bei)/5秒; 持(chi)續:1. 2倍
2.2、輸入(ru)測量(liang)范圍(wei):0 ~ 450V(二次)
2.3、顯(xian)示范圍:0.0 ~ 9999V(接互感器)
2.4、精度: 0. 5%,真(zhen)有效值測(ce)量
2.5、上下限報警(jing)繼電器:常開接點(dian),接點(dian)容量3A/250V,各相報警立計(ji)算,三相共用上限和下限繼電器(qi)輸(shu)出。
2.5.1、上限(xian)報警(jing)輸出條(tiao)件(jian):(1)報(bao)警上限整定值(zhi)有效
(2)當測(ce)量值≥上限(xian)報警設定值時,報警繼電(dian)器動(dong)作輸出;
(3)退出條(tiao)件:測量(liang)值(zhi)≤上限報警(jing)設定值(zhi)-上限回滯(zhi)值(zhi)(上限回滯(zhi)值(zhi)=上限報警(jing)設定值(zhi)×回差整定值(zhi))
2.5.2、下限報警輸出(chu)條件:(1)報警下限整定值有效
(2)當測(ce)量值≤下限報(bao)警(jing)設定(ding)值時(shi),報(bao)警(jing)繼電器動作輸出;
(3)退出條件(jian):測(ce)量值(zhi)≥下(xia)(xia)限(xian)報警設定值(zhi)+下(xia)(xia)限(xian)回滯(zhi)值(zhi)(下(xia)(xia)限(xian)回滯(zhi)值(zhi)=下限報(bao)警設定值(zhi)×回差整定值(zhi))
2.6、不平衡報警:繼電(dian)器輸(shu)出方式:組常開接點(dian),接點(dian)容(rong)量:3A/220V
不平(ping)衡度(du)=(三相電壓(ya)(ya)中項電壓(ya)(ya) - 三相電壓(ya)(ya)中小項電壓(ya)(ya))/項電壓*100%
當不平(ping)衡度(du)>=不平(ping)衡整定值時,報(bao)警(jing)繼電器動作輸出,當不平(ping)衡度(du)<不平(ping)衡整定值時,報(bao)警(jing)繼電器復歸
2.7、工作電源及(ji)功耗:AC ( 85~265)V或DC ( 100~275)V ≤5VA